To upgrade from v7:40:
[LAN]EarliestLegacyVersion = 7400.
Restart the servers after adding the parameter for the changes to take effect.
Wait for the synchronization process to finish; this will depend upon the size of your alarm database. The synchronization information is available from the main kernel window of the Alarm Process as well as the syslog.
The v2018 Summary feature will be disabled when connecting to a v7.40 server. You may still see summary records for active alarms.
When doing an online upgrade from v7.40 to v2018 check that any pre-7.20 Alarm Save files are removed from the v2018 project folders (e.g. <project_cluster>_ALMSAVE.DAT and <project_cluster>_ALMINDEXSAVE.DAT).
Set the [Alarm.<Cluster Name>.<Server Name>]ArchiveAfter .INI parameter to a date prior to the earliest historical event date from which you want to migrate.
Published June 2018