Getting Started > Upgrading to Citect SCADA 2018 > Online Upgrade > Upgrading from v2015

Upgrading from v2015

To upgrade from v2015:

  1. Check that you have SP1, Patch 6 or later installed. For instructions on upgrading to this version, refer to the v2015 documentation.
  2. Check that you have added the following parameters on the .INI file to all your server nodes before you start the online upgrade.

[LAN]EarliestLegacyVersion = 7500.

Restart the servers after adding the parameter for the changes to take effect.

  1. Shutdown SCADA runtime on the primary server
  2. Upgrade Citect SCADA on this server according to the offline upgrade procedure.
  3. Place the backed-up Alarm database in the [CtEdit]Data directory. This will allow a quicker synchronization of alarm servers.
  4. Restart the primary server, which is now upgraded.
  5. Citect SCADA 2018 server will synchronize its alarm database with the running v2015 server. You need to wait for the synchronization process to finish, and this will depend on the size of your alarm database. The synchronization information is available from the main kernel window of the Alarm Process as well as the syslog.
  6. Upgrade your client nodes one by one.
  7. Shutdown runtime on the standby server.
  8. When the newly upgraded v2018 server assumes the primary server role it will migrate the entire alarm database to the new format, and you should now be able to see Alarm Summary data on all migrated Clients.
  9. Upgrade Citect SCADA on this server according to the offline upgrade procedure.
  10. Restart the standby server, which is now upgraded.
  11. Check functionality of the system as a whole.
  12. Test redundancy by switching off the primary server and assuring standby takes over and Clients switch over.

Special Considerations

Published June 2018