TagBrowseOpen Fields

Field Name

Description

Length

Values

ARR_SIZE

Array size

 

Integer (1 means it is not an array)

CLUSTER

The cluster the tag exists on

32

 

COMMENT

Comment

64

If hardware alarm = "".

Or configured event description or trend comment

CUSTOM1

Alarm custom field #1

64

 

CUSTOM2

Alarm custom field #2

64

 

CUSTOM3

Alarm custom field #3

64

 

CUSTOM4

Alarm custom field #4

64

 

CUSTOM5

Alarm custom field #5

64

 

CUSTOM6

Alarm custom field #6

64

 

CUSTOM7

Alarm custom field #7

64

 

CUSTOM8

Alarm custom field #8

64

 

DEADBAND

Alarm deadband

12

For Analog, and Timestamped Analog alarms: Numeric value (real)

ENG_FULL

The engineering full scale for this value

11

Numeric value (real)

ENG_UNITS

Engineering units

8

The predefined values (see below) are in the Help.dbf of the bin directory but the user may specify it as a free text:

%, Amps, deg, ft, ft/min, ft/s, ft/sec, gal, gal/h, gal/min, gal/s, gal/sec, Hz, kg, kg/h, kg/min, kg/s, kg/sec, km/h, kPa, kW, litres, lt, lt/h, lt/min, lt/s, lt/sec, m/min, m/s, m/sec, metres, Rev, Rev/h, RPM, t, t/h, Tonnes, Volts, Watts.

ENG_ZERO

The engineering zero scale for this value

11

Numeric value (real)

EQUIPMENT Name of Equipment 254  

FORMAT

Alarm format

12

For Analog, and Timestamped Analog alarms: Numeric value (real)

FULLNAME

Event user full name

20

For non-Hardware alarms the configured full name of the event user if exists.

Otherwise "System".

RAW_FULL

The raw full scale for this value

11

Numeric value (real)

RAW_ZERO

The raw zero scale for this value

11

Numeric value (real)

SCALED_TYPE

PSI type code (of a scaled value, if scaling is applicable)

 

Integer

TAG

Tag name

80

 

TYPE

Alarm, Trend or Tag type string

16

For Alarms:

"DISABLED", "UNACKNOWLEDGED", "ACKNOWLEDGED", "CLEARED"

For Trends:

"1" - Periodic, "2" - Event, "3" - Periodic Event
For Tags:
RDT_DIGITAL 0
RDT_INTEGER 1
RDT_REAL 2
RDT_BCD 3
RDT_LONG 4
RDT_LONG_BCD 5
RDT_STRING 7
RDT_BYTE 8
RDT_UINTEGER 10
RDT_ULONG 18

Click to return to Browse Function Field Reference

Published June 2018