TrnBrowseOpen Fields

Field Name

Description

Length

Values

ACQERROR

Acquisition Error

6

Numeric value (integer)

AREA

Alarm area

16

Numeric value (integer)

CLUSTER

The cluster the tag exists on

32

 

COMMENT

Comment

64

If hardware alarm = "".

Or configured event description or trend comment

DEADBAND

Alarm deadband

12

For Analog, and Timestamped Analog alarms: Numeric value (real)

ENG_FULL

The engineering full scale for this value

11

Numeric value (real)

ENG_UNITS

Engineering units

8

The predefined values (see below) are in the Help.dbf of the bin directory but the user may specify it as a free text:

%, Amps, deg, ft, ft/min, ft/s, ft/sec, gal, gal/h, gal/min, gal/s, gal/sec, Hz, kg, kg/h, kg/min, kg/s, kg/sec, km/h, kPa, kW, litres, lt, lt/h, lt/min, lt/s, lt/sec, m/min, m/s, m/sec, metres, Rev, Rev/h, RPM, t, t/h, Tonnes, Volts, Watts.

ENG_ZERO

The engineering zero scale for this value

11

Numeric value (real)

EQUIPMENT Name of Equipment 254  

EXPRESSION

Logged variable name

65

The logged variable name (clustername.tagname).

If the expression contains simple Cicode containing a single tag name, such as "LT131" or "LT131<1000", the tag name is returned (in both these cases LT131). If the expression contains a function call or more than one tag name, an empty string is returned.

FILENAME

File where the trend data is to be stored

231

 

FILES

The number of history files stored on the hard disk (for this tag)

4

 

LSL

Lower specification limit

16

 

NAME

Alarm name

80

 

PRIV

Alarm privilege

16

Numeric value (integer)

PSI_TYPE

PSI type code

 

Integer

RANGE

Process range

16

 

SAMPLEPER

Sample period of the trend in seconds

16

Numeric value (real)

SCALED_TYPE

PSI type code (of a scaled value, if scaling is applicable)

 

Integer

SDEVIATION

Standard deviation

16

 

SPCFLAG

Indicates tag is a Statistical Process Control (SPC) tag

   

STORMETHOD

Storage method for the SPC data

16

"Scaled" or "Floating Point"

SUBGRPSIZE

The size of each subgroup

8

 

TAG

Tag name

80

 

TAGGENLINK

Indicates Tag was imported from an IO Device

 

Name of the IO Device from which this tag was generated

TIME

Alarm Time

12

hh:mm:ss [am|pm].

Note: works between: UTC time 1/1/1980 - UTC time 31/12/2037, otherwise ""

TRIGGER

(trend fields)

The variable tag that triggers data logging

65

The variable tag (clustername.tagname) that triggers data logging.

If the trigger contains simple Cicode containing a single tag name, such as "LT131<50", the tag name is returned (in this case LT131). If the expression contains a function call or more than one tag name, an empty string is returned.

TYPE

Alarm, Trend or Tag type string

16

For Alarms:

"DISABLED", "UNACKNOWLEDGED", "ACKNOWLEDGED", "CLEARED"

For Trends:

"1" - Periodic, "2" - Event, "3" - Periodic Event
For Tags:
RDT_DIGITAL 0
RDT_INTEGER 1
RDT_REAL 2
RDT_BCD 3
RDT_LONG 4
RDT_LONG_BCD 5
RDT_STRING 7
RDT_BYTE 8
RDT_UINTEGER 10
RDT_ULONG 18

USL

Upper specification limit

16

 

XDOUBLEBAR

Process mean

16

 

Click to return to Browse Function Field Reference

Published June 2018