System Projects Reference > Situational Awareness System Projects > Situational Awareness Library Project > Equipment Running States
Equipment Running States

Equipment Running State Indicators use the following symbols to indicate the operational state of a piece of equipment. The RunStatus tag is used for indicating out-of-service states with Equipment Running State value of 2, 3 or 4.

OOS and OOSDisabled are digital tags that drive the value of equipment running states.

Equipment Running State

Symbol

Description

0

Default

1

Mnemonic

2

Mnemonic Out of Service - set manually

3

Out To Maintenance / Out Of Service / LOTO (Unavailable)

4

Off / Closed and Selected Out of Service by upstream equipment

5

Off / Stopped and available (Drives) Fully closed (Valves)

6

Drive running as standby drive in a duty standby arrangement

7

Running Forward (Single Speed Drive)
Running Forward Slow Speed (Dual Speed Drive)
Valve Open (MOV)
Valve stopped midway (complex MOV)

8

Running Reverse (Single Speed Drive)
Running Reverse Slow Speed (Dual Speed Drive)

9

Running Forward at Full Speed (Dual Speed Drives)
Valve Fully Open

10

Running reverse at Full Speed (Dual Speed Drives)

11

Interlock bypassed and off/stopped/closed

12

Interlocked and off/stopped/closed

13

Interlock bypassed and on/running/open

14

Interlocked and on/running/open

15

Running Forward at Full Speed (Dual Speed Drives) with an Interlock Bypass Active.

16

Fully Open and Interlocked (Fail Open Valves).

17

State changing from Stopped to Running (Single speed Drive)
State changing from Stopped to Running Slow (Dual speed Drive)
Valve requested to open but still at closed limit

18

State changing from Running Slow to Running Fast (Dual Speed Drive)
Valve requested to open and has left the closed limit

19

State changing from Running to Stopped (Single Speed Drive)
State changing from Running Slow to Stopped (Dual Speed Drive)
Valve requested to close and has left the open limit

20

State changing from Running Fast to Running Slow (Dual Speed Drive)
Valve requested to close but still at open limit

21

Startup Warning Siren

22

Interlocked by a sequence and not running
23 On / Open and Out to Maintenance / Out of Service

24

Off / Closed and Selected Out of Service by upstream equipment

Published June 2018