Extensibility > CtAPI > Function Reference > AlmQuery

AlmQuery

Provides an interface into the alarm summary archive from external applications, replacing the old CtAPIAlarm query. AlmQuery performs significantly better than CtAPIAlarm.

Note: As part of 2018 the AlmQuery function has been re-implemented to return results based on the sequence of events (SOE) page. The format of the result has not been modified and is compatible with 7.20. The re-implementation includes:

AlmQuery is performed through the same mechanism as CtAPIAlarm. To establish the query and return the first record, you call ctFindFirst. Then, to browse the remaining records, you call ctFindNext. To access the data of the current record, ctGetProperty is called for each field of the record.

ctFindFirst is called with the following parameters:

The szTableName is the command string for the query and contains the parameters for the query.

Syntax

`ALMQUERY,Database,TagName,Starttime,StarttimeMs,Endtime,EndtimeMs,Period'

Note: Arguments need to be comma-separated. Spaces between argumentsValues (or variables) passed in a key sequence to a keyboard command in runtime (as operator input). Arguments can also be the values (or variables) passed to a Cicode function when it executes. are supported but not necessary. We recommend no spaces between arguments as they require more processing and take up more space in the query string.

Database:

The Alarm database that the alarm is in (alarm type). The following databases are supported: DigAlm (Digital), AnaAlm (Analog), AdvAlm (Advanced), HResAlm (Time Stamped), ArgDigAlm (Multi-Digital), TsDigAlm (Time Stamped Digital), TsAnaAlm (Timestamped Analog).

TagName:

The Alarm tag as a string.

Starttime:

The start time of the alarm query in seconds since 1970 as an integer in UTC time.

StarttimeMs:

The millisecond portion of the start time as an integer. It is expected to be a number between 0 and 999.

Endtime:

The end time of the alarm query in seconds since 1970 as an integer in UTC time.

EndtimeMs:

Millisecond portion of the end time as an integer. It is expected to be a number between 0 and 999.

Period:

Time period in seconds between the samples returned as a floating point value. The only decimal separator supported is the `.'.

Return Value

The maximum number of samples returned is the time range divided by the period, plus 3 (one for the sample exactly on the end time, and two for the previous and next samples).

Note: Divide the period evenly into the time range, otherwise one extra sample may be returned.

The AlmQuery does not return interpolated samples in periods where there were no alarm samples. However, to stay within the allowable number of samples, the raw alarm samples will be compressed when more than one sample occurs in one period.

When this compression occurs, the returned sample is flagged as a multiple sample. The timestamp is then an average of the samples within the period. The value and comment returned reflects that of the last sample in the period.

The following properties are returned for each data record of the query.

bGood (Bit 0)- Future use only, intended to show when the quality of the alarm data goes bad. At the moment every sample has this bit set to 1 to say the sample is good.

bDisabled (Bit 1)- 1 if the alarm is disabled at the sample's time, 0 otherwise.

bMultiple (Bit 2)- 1 if the alarm sample is based on multiple raw samples, 0 if it is based on only 1 raw sample.

bOn (Bit 3)- 1 if the alarm is on at the sample's time, 0 otherwise.

bAck (Bit 4)- 1 if the alarm is acknowledged at the sample's time, 0 otherwise.

state (Bits 5 - 7)- Contains the state information of the alarm at the sample's time.

The alarm state represents the different states of the different alarm types. The state only contains relevant information if the alarm is on.

For analog, and time-stamped analog alarmsTime stamped analog alarms work in the same way as analog alarms except that they are time stamped (with the Alarm On and Alarm Off times) using millisecond precision from the time kept by the field device (i.e. the RTU or PLC). The configuration details for time stamped analog alarms are exactly the same as for analog alarms. the state can be as follows:

For Multi-Digital Alarms the state can be as follows:

For the rest of the alarm types ignore the state information.

Published June 2018