Before configuring the runtime only environment, and running the Setup Wizard, it is assumed you have transferred a project from the configuration environment, including compiled projects to your local machine. If not refer to Backing up a project for more information.
Using the .CTZ files from your backup included projects and target project, you can restore the project. It is recommended you restore the included project before the target project. The restore project tool is available from the start menu shortcut Runtime Configuration | Project restore
In the Project Restore dialog :
You are now ready to run the Setup Wizard available from the start menu shortcut Runtime Configuration | Citect SCADA Computer Setup
In the RUN path edit box enter, or use the select button to browse for, the path to the local project that you wish to the client to run.If you enter the run path set the run folder under the ‘User’ Folder.
If you wish to maintain a synchronized local version of an external project select the Enable RUN/COPY deployment check box. Then in the COPY path edit box enter, or use the select button to browse for, the path to the external project that you wish maintain synchronization. This feature uses the
Note: The Run/Copy mechanism does not transfer custom files such as meta-data, icons, images or runtime DBF files. Therefore, it is recommended deploying a project before Run/Copy to help ensure that those files at least exist. You will still need to re-deploy a project, when you want to update the custom files.
See Also
Published June 2018