Cicode Programming Reference > Cicode Function Categories > Alarm Functions > AlarmDisableTag

AlarmDisableTag

Disables alarms by Tag on both the Primary and Standby Alarms Servers.

If this function is not called from a foreground task, it becomes a blocking function.

Syntax

INT AlarmDisableTag(STRING Tag, [, STRING ClusterName] [, INT EndTime [, STRING Comment]]] )

Tag:

A string that identifies the alarm to acknowledge. It can be one of the following:

Specify an empty string (" ") to match all alarm tags.

ClusterName:

The cluster where the tag resides.

EndTime:

A date/time variable that indicates when the alarm will no longer be disabled. If this parameter is omitted or set to 0, the alarm will be disabled indefinitely.

Comment:

An optional comment explaining why the alarm is disabledAn optional comment limited to 200 characters explaining why the alarm is disabled. If the comment exceeds 200 characters, hardware error 274 ("Invalid argument passed") will be displayed.

Return Value

0 (zero) if successful, otherwise an error code is returned.

Related Functions

AlarmAckTag, AlarmEnableTag, AlarmClearTag

Example

// Disable alarm for the next 60 minutes
nEndTime = DateAdd(TimeCurrent(), 3600);
AlarmDisableTag("ALARM_1", "Cluster1", nEndTime, "Shelve alarm for 60 minutes.");

// Disable alarm until 20 Dec 2016 6:30am local time
nEndTime = DateAdd(StrToDate("20/12/2016"), StrToTime("6:30"));
AlarmDisableTag("ALARM_1", "Cluster1", nEndTime, "Shelve alarms until 20 Dec 2016 6:30am");

See Also