The AlmFilterEditClose function removes the session from the memory. The filter is not reset and is valid until a new filter is created and applied.
Syntax
INT AlarmFilterEditClose(INT hSession)
Session
Session handle for the historical list previously returned by the function AlarmFilterEditOpen().
Return Value
0 (zero) if the alarm filter session exists, otherwise an error code is returned.
Example
iHndl = AlarmFilterEditOpen(iAN); iRet = AlarmFilterEditSet(iHndl,"Tag=Dig*;Category=1;Area=1;"); iRet = AlarmFilterEditAppend(iHndl, "Priority<20"); sRet = AlarmFilterEditFirst(iHndl); // Tag=Dig*; sRet = AlarmFilterEditNext(iHndl); // Category=1; sRet = AlarmFilterEditLast(iHndl); // Priority<20; sRet = AlarmFilterEditPrev(iHndl); // Area=1; iRet = AlarmFilterEditClose(iHndl);
Related Functions
See Also
Published June 2018