Cicode Programming Reference > Cicode Function Categories > Alarm Filter Functions > AlarmFilterEditPrev

AlarmFilterEditPrev

This function takes a session handle parameter. It gets the previous part of the filter. Each part is either:

Syntax

STRING AlarmFilterEditPrev(INT hSession )

Session:

Session handle for the historical list previously returned by the function AlarmFilterEditOpen().

Return Value

Previous part of filter or if does not exist an empty string "".

Example

iHndl = AlarmFilterEditOpen(iAN);
iRet = AlarmFilterEditSet(iHndl,"Tag=Dig*;Category=1;Area=1;");
iRet = AlarmFilterEditAppend(iHndl, "Priority<20");
sRet = AlarmFilterEditFirst(iHndl);	// Tag=Dig*;
sRet = AlarmFilterEditNext(iHndl);	// Category=1;
sRet = AlarmFilterEditLast(iHndl);	// Priority<20;
sRet = AlarmFilterEditPrev(iHndl);	// Area=1;
iRet = AlarmFilterEditClose(iHndl);

Related Functions

AlarmFilterEditFirst, AlarmFilterEditNext, AlarmFilterEditLast

See Also

Alarm Filter Functions

Published June 2018